Roof Load Calculator for Solar Panels
Roof Load Check Calculator
Verify solar panel + mounting dead load against the allowable structural capacity of the roof. Adjust any input and the result updates live.
Inputs
Updates liveFrom the roof's structural drawings or engineer. IS 875 (Part 2) Table 2 design values: flat roof with access 1.5, without access 0.75, sloping over 10° 0.75 less 0.02 per degree (min 0.4).
Results
LiveWithin capacity · ample headroom
Dead Load
kN/m²
Total Load
kN/m²
Allowable
kN/m²
Safety Factor
ratio
Assessment
Structurally comfortable ✓
“IS 875 (Part 2) Table 2, imposed loads on roofs up to 10° slope: 1.5 kN/m² with access, 0.75 kN/m² without; over 10°, 0.75 kN/m² less 0.02 per degree, minimum 0.4. This check compares the added solar load plus the remaining imposed load with the roof's design imposed load; a structural engineer must confirm.”
About the Roof Load Check
A roof-load check verifies that the structure can safely carry the extra dead load of the solar array (modules, mounting structure, and any ballast) plus the wind and live loads it induces, before installation. It compares the added load per square metre against the roof type's allowable capacity.
Last updated · How we build our calculators
Formula
Added dead load (kg/m²) = Array weight (kg) ÷ Array footprint (m²)
- Array weight
- Modules + mounting structure + ballast (kg)
- Array footprint
- Plan area the array covers (m²)
How to calculate it
- 1Estimate the array's weight: modules plus mounting structure plus any ballast.
- 2Divide by the area it covers for the added dead load (kg/m², or kN/m² ÷ 102).
- 3Find the roof's design imposed load: IS 875 Part 2 Table 2 gives 1.5 kN/m² for flat roofs with access and 0.75 kN/m² without (up to 10° slope).
- 4Check the added solar load plus the imposed load that remains on the covered area against that design load; a structural engineer must confirm, and sheet or timber roofs need a purlin or rafter check.
Worked example
A flush RCC rooftop system typically adds only ~15–25 kg/m² of dead load — comfortably within a designed RCC slab's capacity. A ballasted flat-roof mount can add more and must be checked; a light sheet-metal or asbestos roof usually needs structural reinforcement first.
What you can calculate
- RCC / PEB / Timber
- kN/m² check
- System load
- Pass/Fail
Standards & references
Frequently asked questions
How much weight does rooftop solar add?
A flush-mounted rooftop system adds roughly 15–25 kg/m² — light relative to a designed RCC roof. Ballasted mounts on flat roofs add more (the ballast resists wind uplift), so those always warrant a structural check.
Can any roof support solar panels?
RCC roofs almost always can. Pre-engineered/sheet-metal roofs depend on purlin spacing and gauge. Old asbestos, fragile, or corroded roofs often cannot and need reinforcement or replacement first. A quick structural assessment per IS 875 settles it before installation.
Ready to build your solar project?
Get free quotes from verified EPCs and installers across India.
You might also need
Pedestal Height
Calculate front and rear pedestal heights for target module tilt on flat rooftops
OpenModule Layout Planner
Plan tables, rows and string configuration for a rooftop array
OpenSetback from Parapet
Calculate minimum module setback from parapet walls to avoid shading
OpenBallast Weight
Calculate ballast required to resist IS 875 Part 3 wind uplift without penetrations
OpenWind Load (Rooftop)
Calculate uplift and lateral wind forces on rooftop PV modules per IS 875 Part 3
OpenAnchor Bolt Sizing
Check anchor bolt steel tension (IS 800) against factored wind uplift and count the bolts
Open